PRODUCTS
Air cooled top suction HX-NDF
The entire machine has been carefully designed with a 10% margin on the basis of the design, ensuring a stable dew point at the equipment outlet
Adopting internationally renowned refrigeration compressors, stable operation, low noise, low energy consumption, and reliable safety;
The main refrigeration accessories are selected from the DANFOSS brand;
The part where the air flows through is treated with spray coating to avoid secondary pollution of compressed air;
Efficient gas water separation, avoiding secondary evaporation of water, and more thorough discharge of pollutants;
Optional linkage interface and dew point detection function;
Has multiple fault alarm and processing functions;
Electronic drainage system, not easily clogged, ensuring the best drainage effect of the unit;
Integrated design, compact and reasonable structure, easy to operate and maintain, and easy to install.
Technical parameter
Processing capacity | See specification sheet for details | |
Container design pressure | 1.0MPa | |
Rated working pressure | 0.7MPa | |
Maximum allowable working pressure | 0.4~0.95MPa(accept orders outside of scope) | |
System pressure drop | ≤0.018MPa | |
Rated intake temperature | ≤45℃ | |
Ambient temperature | ≤40℃ | |
Inlet oil content | ≤5ppm | |
Dew point of exhaust pressure | 2~10℃ | |
Heat exchanger assembly | Type | Shell and tube type |
Main materials | Efficient copper tube, aluminum foil, carbon steel | |
Structure | Multi process (including pre cooling and reheating) | |
Condenser | Type | Finned type |
Main materials | Efficient copper tube and aluminum foil | |
Cooling method | Forced air cooling | |
Power Mode | See specification sheet for details | |
External dimensions | See specification sheet for details | |
Conditions of Use | A place with good ventilation and no dust or oil stains | |
Installation method | Indoor installation, site leveling, no need for foundation |